Taco 3350-T3 Installation Guide Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Installation:
1. Install the valve in the direc-
tion indicated by the flow
arrows on the body. The
valve can be installed in any
orientation. Rotate the set
point indicator so that the
pressure setting is always
visible (figure 1).
2. The 3350 PRV connects via a
1
2
" NPTF on the outlet and
may be connected using either
the
1
2
" NPTF or the Taco union
threads on the inlet. The Taco
union threads are more com-
monly used on existing installations already connected
by a union nut. To use the union connection, remove the
plastic thread protector on the valve inlet and connect
the existing union nut. Replace the old union gasket with
the new one supplied with the 3350.
Note: This product should be installed by profession-
als familiar with the correct function and performance
of hydronic heating systems and their associated
components.
Caution: Protect the 3350 from freezing and exposure
to chemicals or solvents.
Adjusting the Set Presure:
1. Turn the green locknut counter clockwise to loosen
(figure 2).
2. Turn the adjustment knob (figure 3) counter clockwise to
reduce pressure or clockwise to increase the pressure
until the indicator points to the desired pressure setting.
3. The PRV does not release pressure. When adjusting
to a lower setting any excess pressure will need to be
released through a suitable release point. Turn the
green locknut clockwise until finger tight.
Fast Fill:
The 3350 is equipped with an
automatically resetting fast fill fea-
ture. The fast fill overrides the set
pressure during filling and purging
of the system. To activate the fast
fill simply push in the button
marked fast fill located on top of
the PRV (figure 4). When the set
pressure is reached the fast fill
button will pop out. The valve is
now out of the fast fill mode and
back into the normal operating
mode.
NOTE: If the fast fill button is unintentionally pushed in
prior to installation it may be returned to the normal
operating mode as follows.
1. Unscrew and remove the lock knob carefully so as not
to lose the spring.
2. If the spring is still inside the lock knob remove it.
3. Using a suitable tool, such as a small screwdriver or pen,
reach inside the lock knob and push the button back out.
4. Put the spring back into the lock knob and screw the
knob back onto the cartridge.
Maintenance:
To clean the integrated strainer in
the pressure reducing valve, close
the isolating valve upstream of the
unit. Remove the PRV cartridge by
turning the black 8 point cam nut
on the cartridge counter clockwise
and pull out. Clean with water
only. Reverse the procedure to
install (figure 5).
Caution: Do not over tighten the
cartridge as this may damage
the threads in the new cartridge
or in the valve body and require
that they be replaced.
Application:
Taco’s PRV (Boiler Feed Valve) is designed for use in
today’s Hydronic heating systems. The model 3350 PRV
reduces incoming pressure and automatically maintains
the system pressure to the valve’s adjustable set point.
If the system pressure drops below the valve’s set point
it will automatically add water to the system. It is suitable
for systems with fill pressure requirements between
10-50 PSI. The Taco PRV showcases a fast fill button
with automatic reset. The valve automatically exits the
fast fill mode once the system is full and the desired set
pressure is reached. No more manually holding the valve
open or locking it in an open position, possibly over
pressurizing to the point of setting off the relief valve.
Installation Diagram:
Figure 2
+
Figure 3
Figure 4
Figure 5
4.3" (110 mm)
2.0"
(51 mm)
removal
space
1
1
4-14 UNS-2A
1
2-14 NPT
0.7"
(17.8 mm)
1.5"
(38.1 mm)
3.5"
(90 mm)
0.7"
(17.8 mm)
1
2-14 NPT
Dimensions:
360°
Figure 1
Page view 1
1 2

Comments to this Manuals

No comments